WYLEX NHX Series
WYLEX NHX Series MCBs, RCBOs & associated RCDs.
Current range of WYLEX BSEN60898 MCBs for domestic & light commercial use. Not suitable for fixed busbar teeth of WYLEX TPN boards, does however use a toothed busbar
Popular in social housing/council specifications, there are a great number of WYLEX boards installed with NHX circuit protection across the UK.
NHX series circuit breakers are 6000A breaking current (6kA) and the range is as follows:
- 60898 Type B MCB = 6A, 10A, 16A, 20A, 32A, 40A, 50A
- 60898 Type C MCB = 6A, 10A, 16A, 20A, 32A, 40A, 50A
- 61009 Type B RCBO = 6A, 10A, 16A, 20A, 32A, 40A, 50A
- 61009 Type C RCBO = 6A, 10A, 16A, 20A, 32A, 40A, 50A
NHX Type B MCB Specifications
Breaking Capacity According to BS EN 60898 & IEC 60898: 6kA (6000A)
Rated Voltage: 230V / 400V AC
Maximum Operating Temp: 55 degrees C
Part Numbers:
- NHXB6 – 6A Type B MCB
- NHXB10 – 10A Type B MCB
- NHXB16 – 16A Type B MCB
- NHXB20 – 20A Type B MCB
- NHXB32 – 32A Type B MCB
- NHXB40 – 40A Type B MCB
- NHXB50 – 50A Type B MCB
NHX Type C MCB Specifications
Breaking Capacity According to BS EN 60898 & IEC 60898: 6kA (6000A)
Rated Voltage: 230V / 400V AC
Maximum Operating Temp: 55 degrees C
Part Numbers:
- NHXC6 – 6A Type C MCB
- NHXC10 – 10A Type C MCB
- NHXC16 – 16A Type C MCB
- NHXC20 – 20A Type C MCB
- NHXC32 – 32A Type C MCB
- NHXC40 – 40A Type C MCB
- NHXC50 – 50A Type C MCB
NHX MCB Dimensions (Both Type B & Type C)
Both B & C type MCBs share the same dimensions as each other.
All MCBs & RCBOs share the same single module (1P) width
The height (top to bottom) is: 89mm
The ‘Depth’ which is the total front-to-back measurement (furthest point above shoulder of din rail connection): 70mm
The depth of the busbar connection from the front face of lower part of MCB: approx 29~30mm
Busbar connection is by cage clamp to front. Also has cut outs at the front for busbars which screw to the MCB instead of the toothed busbar.
Note clamp leaves gap at back, beware that busbar tooth is correctly located in MCB and not behind the cage clamp during assembly/re-assembly
NHXSBS1 Type B RCBO Specifications
Breaking Capacity According to BS EN 61009 & IEC 61009: 6kA (6000A)
Rated Voltage: 230V / 400V AC
Maximum Operating Temp: 55 degrees C
Part Numbers:
- NHXSBS1B06 – 6A Type B 61009 RCBO
- NHXSBS1B10 – 10A Type B 61009 RCBO
- NHXSBS1B16 – 16A Type B 61009 RCBO
- NHXSBS1B20 – 20A Type B 61009 RCBO
- NHXSBS1B32 – 32A Type B 61009 RCBO
- NHXSBS1B40 – 40A Type B 61009 RCBO
- NHXSBS1B50 – 50A Type B 61009 RCBO
NHXSBS1 Type C RCBO Specifications
Breaking Capacity According to BS EN 61009 & IEC 61009: 6kA (6000A)
Rated Voltage: 230V / 400V AC
Maximum Operating Temp: 55 degrees C
Part Numbers:
- NHXSBS1C06 – 6A Type C 61009 RCBO
- NHXSBS1C10 – 10A Type C 61009 RCBO
- NHXSBS1C16 – 16A Type C 61009 RCBO
- NHXSBS1C20 – 20A Type C 61009 RCBO
- NHXSBS1C32 – 32A Type C 61009 RCBO
- NHXSBS1C40 – 40A Type C 61009 RCBO
- NHXSBS1C50 – 50A Type C 61009 RCBO
Alternative Fitments?
The WYLEX NHX series of circuit breakers & RCBOs use the same toothed busbar and share a similar busbar connection layout as the following:
- WYLEX NSB Series MCBs & RCBOs – Direct Swap
NB: Electrium (the company who manufacture WYLEX) have confirmed to us that the NHX series MCBs are a direct swap for previous NSB series MCBs/RCBOs. They paid us to install NHX MCBs into NSB board during the massive recall completed on their NSB circuit breakers. Indeed if you still come across any of these circuit breakers then Contactum will still pay you directly to swap then on behalf of the customer.
WYLEX Manufacturer Site: WYLEXs manufacturer page
WYLEX NHX Specification Sheet: WYLEX Specifications for the NHX series of circuit protection
Buy NHX MCBs & RCBOs at the following links:
Wylex NHXB06 MCB – Wylex NHXB16 MCB – Wylex NHXB32 MCB – Wylex NHXB40 MCB